Your facility and the protection of those inside can depend significantly on the proper installation of an effective fire protection system. An important aspect of such a system is the fire rated door. When it comes to keeping human life safe and properly protected, these doors are essential elements in an entire fire safety system. With these doors properly in place and installed, they can save lives by preventing a blaze from spreading from one section of the building to another. In addition, they serve as a damper on toxic fumes and smoke emanating from the fire. The way to ensure these doors have been properly installed and are functioning as they are intended is to hire the services of a certified fire door Inspector. Illinois organizations can benefit from the services provided by an experienced inspector in these matters.
Annual inspections are required in the U.S. by the NFPA of fire resistant rated doors and frame assemblies.
A certified fire door Inspector, at a minimum, as required to verify the following items in accordance with NFPA 80.5.2.4:
• The frame, the war, hinges, hardware, and noncombustible threshold are secured and aligned with no indications of damage, and appear to be functioning properly
• The surfaces of the door or the frame show no breaks or holes
• Vision light frames, glazing beads, and glazing are intact, secure, and fastened in place
• No missing or broken parts are present
• Door clearances prescribed in the current section 4.8.4 (3/4” maximum clearance under the bottom of the door) and 6.3.1 (1/8” maximum at the edges and top) are not exceeded at the door frame or the edge of the door, on the pull side of the door
• Gasketing and edge seals are inspected to verify their integrity
• When operated from the full open position, the active door completely closes
• Field modifications which would void the label have been performed on the door assembly
• No installations of auxiliary hardware items that inhibit the operation or interfere with the door or frame have occurred.
• The latching hardware operates correctly and secures the door when the door is in the closed position
• The inactive leaf shuts prior to the active leaf shedding if a coordinator is present
Based on NFPA 80, a certified fire door Inspector Maas inspect fire door assemblies and testing of the door must occur once a year which includes a signed written record of the inspection.
If you are looking for a way to have your fire door assemblies inspected in Illinois, get in touch with a reliable fire protection company today.